Input Parameters

Results

--
Available Reactive Power
kVAR
--
Max Q Absorb (lagging)
kVAR
--
Max Q Inject (leading)
kVAR
--
Operating Power Factor
Note: IEEE 1547-2018 Category II requires Volt-VAR, Volt-Watt, frequency droop, and ride-through. Smart inverters can provide grid support even at night (STATCOM mode) if rated for it.

Reference

Max Q = sqrt(S² - P²) [kVA capacity circle] PF Limit Q = P x tan(acos(min PF)) Available Q = min(Max Q, PF Limit Q) Volt-VAR: absorb Q when V>1.03 pu, inject when V<0.97 pu PF = P / sqrt(P² + Q²)