Input Parameters

Results

--
Volume Per Conductor
in³
--
Required Box Volume
in³
--
Minimum Box Size
--
Ground Conductor Vol
in³
Note: PV junction boxes must be listed for the application and accessible. Use NEMA 3R or 4X rated boxes for outdoor PV installations.

Reference

Volume Per Conductor: 14AWG=2.0, 12=2.25, 10=2.5, 8=3.0 in³ Total = Conductors + Ground(1x) + Devices(2x each) + Clamps(1x) All grounds count as 1 conductor Per NEC 314.16(B)